M3N2R 3*150

Description

Description

Standards

  • Product
    IEC 60228; IEC 60502-2
  • Test
    IEC 60332-1-2; IEC 60332-3

Scope

This specification covers three cores armoured cables, conforming to IEC 60502-2 Specifications.

Construction

2.1 Conductor

Plain, annealed electrolytic copper conductors, circular stranded,conforming to the applicable requirements of IEC 60228.

2.2 Insulation

Extruded inner semi conductive layer, XLPE insulation and  extruded outer semi conductive layer .

2.3 Metallic Screen Layer

Copper tape on each core

2.4 Separation Sheath

Special Hydrocarbon resistant and fire retardant PVC .

2.5 Armour

GALVANIZED STEEL WIRES .

2.5 Sheath

Special Hydrocarbon resistant and fire retardant PVC .

Tests

All tests required by IEC 60502-2 either on Raw material or on finished produc

TEST AT WORKS ARMORED CABLES ACCORDING TO IEC 60502-2 & IEC 60332-3

Routine Tests

 -          Max. DC conductors resistance at 20°C acc. to IEC 60228 & IEC 60502-2 parag.16.1 & 16.2

 -          High voltage test acc. to IEC 60502-2  parag. 16.1 & 16.4

 -          Max. partial discharge test  at 1.73 Uo acc. to IEC 60502-2  parag.16.1 & 16.3

Liban Cables will carry out these tests on all the lengths and tests certificates will be provided.

 

Sample Tests

 -          Check of the build - up and color coding of the cable                                                      

 -          Check of dimensions 

            Insulation                      :           according to IEC 60502-2           Parag.  17.5.2

            Separation sheath         :           according to IEC 60502-2           Parag.  17.5.3

            Armouring                     :           according to IEC 60502-2          Parag.  17.7

            Oversheath                   :           according to IEC 60502-2           Parag.  17.5.3

-           Hot Set Test                  :           according to IEC 60502-2           Parag.  17.10

These tests will be carried out on one length of each size during each inspection .

Tests certificates will be provided by Liban Cables

 

Type Tests

Mechanical characteristics on insulation and sheaths material (tensile strength and elongation at break) in accordance with IEC 60502-2.

Fire retardance test according to IEC 60332-3.

These tests will be carried out on one length of the order .

Tests certificates will be provided by Liban Cables

DRAWING MV 3C GSWA ARMORED

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Copper
Conductor shape
Circular
Material of the inner semi-conductor
Extruded
Insulation
XLPE
Material of the external semi-conductor
Extruded fully bonded
Screen
Copper tape
Armour type
Galvanized steel wires
Outer sheath
Special PVC compound
Colour
Red
Conductor flexibility
-

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
150 mm²
Conductor diameter
14.2 mm
Nominal insulation thickness
3.4 mm
Nominal armour wire diameter
2.5 mm
Nominal outer sheath thickness
3.1 mm
Nominal outer diameter
64.0 mm
Approximate net weight
9508 kg/km

Electrical characteristics

Electrical characteristics

Test voltage
21 kV
Rated Voltage Uo/U (Um)
6 / 10 (12) kV
Perm current rating in air 30°C
397 A
Permissible current rating when buried
332 A
Max. DC resistance of the conductor at 20°C
0.124 Ohm/km
A.C. Conductor resist. 50Hz and at 90 °C
0.159 Ohm/km
Permissible short circuit current conductor 1s
21.8 kA
Thermal soil resistivity wet zone
1.5 °K.m/W

Mechanical characteristics

Mechanical characteristics

Cable flexibility
7xD
Mechanical resistance to impacts
Good

Usage characteristics

Usage characteristics

Fire retardant
IEC 60332-3
Flame retardant
IEC 60332-1-2
Laying depth, center of system
800 mm
Ambient air temperature
30 °C
Ambient ground temperature
20 °C
Max. conductor temperature in service
90 °C
Operating temperature, range
-15 ... 55 °C
Short-circuit max. conductor temperature
250 °C
U.V resistance
Yes

Resources

Resources

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close